Lighting Layout Basics

Spacing, uniformity and the lumen method.

1. Why it matters

A lighting layout turns a target illuminance into a fixture count and spacing that actually delivers it on the working plane — evenly, without dark gaps or glare. Get the layout right and you buy fewer fixtures that light the space correctly; get it wrong and you either over-spend on lumens or hand the client a room that fails its lux requirement on day one.

Design to a target lux with a maintenance factor, keep spacing within the fixture's SHR, and check uniformity — not just average lux.

2. Start from the required illuminance

Every layout begins with the maintained illuminance the task needs, taken from a standard such as EN 12464-1 (Europe) or the IES Handbook (North America). Design to the maintained value, applying a maintenance factor (typically 0.7-0.8) so the space still meets target at end of life, not just when new.

SpaceTypical maintained lux
Warehouse aisles / storage150-200 lx
General office / open plan300-500 lx
Detailed / drawing work750-1000 lx
Retail sales floor300-750 lx (+ accent)
Car park / circulation75-100 lx

3. Spacing, mounting height and uniformity

Spacing is not free — it is bounded by the fixture's spacing-to-height ratio (SHR / SHRmax). Exceed it and you get scallops of light and dark between fixtures even if the average lux is fine. Uniformity (Emin/Eavg) is the real quality metric.

  • Keep centre-to-centre spacing ≤ SHRmax × (mounting height above the working plane).
  • Target uniformity Emin/Eavg ≥ 0.6 for task areas, ≥ 0.4 for surrounds.
  • Half-spacing from the walls to avoid dark perimeters.
  • Higher mounting needs narrower beams; low ceilings need wide/batwing optics.

4. Glare, and a quick sanity check

Control glare with UGR (Unified Glare Rating): aim UGR ≤ 19 for offices and screen work, ≤ 22 for industry, ≤ 25 for rough tasks. Before trusting any software, sanity-check fixture count with the lumen method: fixtures ≈ (target lux × area) ÷ (lumens per fixture × utilisation factor × maintenance factor). It will not place the fixtures, but it tells you instantly if a quote's quantity is plausible or padded.

5. Checklist

  • Set the maintained target lux from EN 12464-1 / IES
  • Apply a maintenance factor (0.7-0.8) to design values
  • Keep spacing within the fixture SHRmax
  • Check uniformity Emin/Eavg, not just average lux
  • Hold UGR to the space limit; sanity-check count with the lumen method

6. FAQ

Can I just use the lumen method instead of software?
The lumen method gives a fast, reliable fixture count for a regular rectangular space with a uniform layout, and it is perfect for checking a quote. But it gives an average only — for uniformity, glare and irregular rooms you still need a point-by-point calculation (Dialux, AGi32 or similar).
Why does my space measure below the designed lux?
Common causes: no maintenance factor applied (dirt and lumen depreciation), wrong reflectance values assumed for walls/ceiling, fixtures spaced beyond SHRmax, or the installed lumen output being lower than the datasheet chip figure. Re-measure at the working plane and compare against the maintained, not initial, design.